Honeywell R7861A-1026/U Dynamic Self Check Flame Amplifier

Item SKU - R7861A-1026/U by Honeywell (EDP 934571)

Product Images
Stock / Price Information
Please Login for Pricing

Product Description

Old Number R7861A-1026

Solid state plug in amplifier that responds to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules

Flame failure response time of 2.0 or 3.0 seconds - Flame signal strength ranges from 0.0 to 5.0 Volts DC

Plugs into 7800 relay module through printed circuit board edge connector keyed for proper orientation.

Flame signal test jacks to measure amplifier flame signal voltage - Color coded labels identify flame detection type

Dynamic Self Check Amplifier tests the detectors and all electronic components in the flame detection system

Documentation

Specifications

These specifications are subject to change by the manufacturer, and are only approximate. For precise specifications, please call our inside sales department at 860-221-SALE (860-221-7253).

Approximate Weight (pounds)
.30